(a) Vertical and Horizontal. Signs and outline system enclosures shall have not less than the vertical and horizontal clearances from open conductors specified in the following table:
TABLE 2560.10
CLEARANCES
Vertical clearance above all signs upon which persons can walk..... 8 feet
Vertical clearance above all signs upon which persons cannot walk.. 3 feet
Vertical clearance under signs..................................... 3 feet
Horizontal clearance from signs.................................... 3 feet
(Title 24, Part 3, Section 3-600-10(a).)
(b) Elevation. The bottom of sign and outline lighting enclosures shall not be less than 16 feet above areas accessible to vehicles.
EXCEPTION: The bottom of such enclosures may be less than 16 feet above areas accessible to vehicles where such enclosures are protected from physical damage.
(Title 24, Part 3, Section 600-10(b).)
NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.