This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 1. Low-Voltage Electrical Safety Orders
Article 78. Electrically Driven or Controlled Irrigation Machines
Return to index
New query

§2568.8. Disconnecting Means.


(a) The main disconnecting means for a center pivot irrigation machine shall be located at the point of connection of electrical power to the machine or shall be visible and not more than 50 feet (15.2 m) from the machine.

(b) The disconnecting means shall be readily accessible and capable of being locked in the open position.

(c) A disconnecting means shall be provided for each motor and controller.

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.