Cable connectors, male and female, for flexible conductors shall be so constructed that tension on the cord or cable will not be transmitted to the connections. The female half of the connector shall be attached to the load end of the power cord or cable. The connector shall be rated in amperes and designed so that differently rated devices cannot be connected together. (See Section 2500.10 for pull at terminals.)
(Title 24, Part 3, Section 520-67.)