This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 1. Low-Voltage Electrical Safety Orders
Article 69. Places of Assembly
Return to index
New query

§2551.3. Wiring Methods.


The fixed wiring methods shall be metal raceways, nonmetallic raceways encased in not less than 2 inches of concrete. Type ALS cable, Type CS cable, mineral-insulated metal-sheathed cable, or Type MC cable.

EXCEPTION: No. 1: Nonmetallic-sheathed cable, Type AC metal-clad cable, and rigid nonmetallic conduit shall be permitted to be installed in those buildings or portions thereof that are not required to be fire rated construction by the applicable building code.

EXCEPTION: No. 2: As provided in Article 76, Sound Recording and Similar Equipment, and for communication circuits, remote control and signaling circuits, and for fire protective signaling circuits.

(Fire rated construction is the fire-resistive classification used in building codes.)

(Title 24, Part 3, Section 518-3.)

NOTE: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 18943(c), Health and Safety Code.