This information is provided free of charge by the Department of Industrial Relations from its web site at www.dir.ca.gov. These regulations are for the convenience of the user and no representation or warranty is made that the information is current or accurate. See full disclaimer at https://www.dir.ca.gov/od_pub/disclaimer.html.
 
Subchapter 5. Electrical Safety Orders
Group 1. Low-Voltage Electrical Safety Orders
Article 58. Capacitors
Return to index
New query

§2534.8. Disconnecting Means.



A disconnecting means shall be provided in each ungrounded conductor for each capacitor bank and shall meet the following requirements:

(a) The disconnecting means shall open all ungrounded conductors simultaneously.

(b) The disconnecting means shall be permitted to disconnect the capacitor from the line as a regular operating procedure.

(c) The rating of the disconnecting means shall not be less than 135 percent of the rated current of the capacitor.

Exception: A separate disconnecting means shall not be required where a capacitor is connected on the load side of a motor controller.

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.